Setpoint and temperature compliance · last 13 months
Setpoint compl. (%)
Temp compl. (%)
HVAC operational trend
Trend · 13mo
Runtime (left axis) and cooling ΔT (right axis) · last 13 months
Runtime (h/day)
Cooling ΔT (°F)
Refrigeration trend — monthly averages
Compliance per unit · last 13 months · tooltip shows target and threshold
Trend · 13mo
WIC-1 cooler (≥98%)
FRZ-1 freezer (≥99%)
HVAC KPIs — site averages
Per asset — HVAC
Asset detail — current month
Individual readings · last known values shown in gray for assets with lost connection
Asset
Type
Connection
Data avail.
Runtime
Cooling ΔT
Setpoint compl.
Temp compl.
RTU-1
RTU
Online
4 min ago · Full availability
100%
11.2h
target 8–18h
17.8°F
target 16–22°F
98.7%
day 76°F · night 78°F
93.5%
below 95% threshold
RTU-2
RTU
Online
3 min ago · Full availability
100%
6.2h
below 8h threshold
14.8°F
below 16°F threshold
98.4%
policy followed
88.4%
below 95% threshold
RTU-3
RTU
Online
2 min ago · Full availability
100%
19.6h
above 18h threshold
18.9°F
target 16–22°F
96.8%
policy followed
91.8%
below 95% threshold
Asset telemetry — select asset
RTU RTU-1
RTU RTU-2
RTU RTU-3
Period controlled by topbar selector. Showing:Day
RTU-1 — telemetry · Today (10 min intervals)
All signals overlaid · left axis = temperature (°F) · right axis = power (kW) or compressor
Auxiliary equipment
Optional
Optional assets monitored at this site — DOAS and exhaust fans. These appear only when the site is configured with this equipment.
Per asset — auxiliary
DOAS + exhaust fans · current period
Asset
Type
Connection
Data avail.
State
Runtime
Cycles
DOAS-1
DOAS
Online
3 min ago · Full availability
100%
ON
14.2h
target 8–18h
6
typical 3–6
EF-1
Exhaust fan
Online
2 min ago · Full availability
100%
ON
15.8h
target 8–18h
4
typical 3–6
EF-2
Exhaust fan
Online
4 min ago · Full availability
100%
OFF
12.4h
target 8–18h
24
⚠ short-cycling
Asset telemetry — select asset
DOAS DOAS-1
FAN EF-1
FAN EF-2
Period controlled by topbar selector. Showing:Day
DOAS-1 — telemetry · Today (10 min intervals)
ON/OFF state (left axis) · outside air temp (right axis)
Refrigeration KPIs — site averages
Per asset — Refrigeration
Asset detail — current month
Current temperature + monthly compliance per unit
Asset
Type
Connection
Data avail.
Current temp
Target range
Monthly compliance
Status
WIC-1
Walk-in cooler
Online
6 min ago · Full availability
100%
35.8°F
34–38°F
99.1%
threshold ≥ 98%
In compliance
FRZ-1
Freezer
Online
3 min ago · Full availability
100%
-4.2°F
-10°F – 0°F
99.4%
threshold ≥ 99%
In compliance
Door activity — refrigerationPOC · to be confirmed
Proof of concept — door-open sensor metrics from a reed switch, correlated with unit temperature. Thresholds illustrative, pending validation. The sensor is binary (open/closed only); "closed" does not mean "not leaking".
Per asset — door metrics
Openings, open-time, door-ajar and door-attributed excursions · selected period
Door-open pattern — by hour
Openings per hour-of-day for the worst asset · expected restock peaks vs anomalous spikes
Caveats: binary sensor. "Closed" ≠ not leaking. DAE is an air proxy → manual product check, never auto-condemn. Freezer excursions are quality/frost. % time open = load indicator, not metered energy.
Asset telemetry — select asset
WIC WIC-1
FRZ FRZ-1
Period controlled by topbar selector. Showing:Day
WIC-1 — telemetry · Today (10 min intervals)
Unit temperature and door open/close events over time
ROI summary — Store #214
Cumulative since installation
Savings breakdown — selected period
Energy savings
Calculated
$312/mo
Consumption savings247 kWh · $198
Peak demand reduction2.8 kW · $114
vs M&V baseline · Apr 2023
Avoided truck rolls
Calculated
$168/mo
Events avoided2 this month
Value per event$84(pre-agreed)
Source: ticket platform · remote resolution
Product loss avoided
Coming soon
—
Value not yet calculated · requires refrigeration event log integration
Extended product lifespan
Coming soon
—
Value not yet calculated · requires product category data
Other savings
Coming soon
—
Additional saving categories to be defined
Monthly savings — accumulated · Store #214
Energy savings + avoided truck rolls · since installation
Energy savings
Avoided truck rolls
Monthly savings detail
Month
Energy savings
Avoided truck rolls
Total savings
Accumulated
Note — reference only:All thresholds and ranges are illustrative. Schedule compliance requires on/off schedules to be defined per space before calculation. Parameters must be agreed with each client.
Filter by space:
Site KPIs
Lighting trend — site averages
Trend · 13mo
Schedule, utilization and burn hours over time
Schedule compl. (%)
Utilization (%)
Burn hours (h/day)
Lighting circuits — current state
Per circuit data with current state and monthly compliance
Source:
Bill data is available only for Month / Quarter / YTD.Site type:Conv+Fuel · Cluster:37 sites
Per-metric comparison of meter readings against the utility bill
Metric
Meter
Bill
Δ
Status
Consumption (kWh)
2,782
2,847
+2.3%
Within tolerance
Peak demand (kW)
27.4
28.0
+2.2%
Within tolerance
Tolerance is ±5% (example, configurable). Gaps beyond it flag meter coverage gaps, utility estimated reads, or billing-cycle misalignment.
Monthly evolution — consumption & peakSource: Meter What:Monthly totals over the last 13 months. kWh bars:total consumption per month (left axis). Peak line:max kW reached each month (right axis). Cluster median:dashed line shows the median kWh of the 37 Conv+Fuel sites in your portfolio.
Trend · 13mo
kWh consumption
Peak demand (kW)
Cluster median (kWh)
Consumption by domainSource: Submeters What:Share of total consumption per domain during the selected period. Calc:HVAC and Lighting from their dedicated submeters; "Other" is the main meter minus the submeters (refrigeration, plug loads, etc.). Note:Only available at sites where submeters are installed. Without submeters this card would be hidden.
Hourly pattern —consumptionSource: Meter What:Average kWh (or kW peak) per day-of-week and hour-of-day, aggregated over the selected period. Read it:rows = days, columns = hours. Darker = higher value. Use:spot after-hours consumption, weekend vs weekday differences, start-up spikes.
lowhigh
Detailed telemetrySource: Meter What:15-min interval readings from the selected meter over the selected period. Signals:click chips to show/hide. Each signal renders on the axis matching its units (left = kW/kVAR/kWh, right = A/V/PF). Meter:if the site has multiple meters (e.g., revenue + submeters), pick which stream to view.
Select meter
Signals:
Alarm to ticket funnel
Tickets by origin · April 2026
Tickets by resolution · April 2026
Tickets by system · April 2026
Tickets by criticality · April 2026
Alarms vs tickets — monthly volume
Trend · 13mo
Bars show alarm volume (left axis), line shows tickets generated (right axis) · last 13 months
Alarms (BMS + FDD)
Tickets generated
Proactive vs Reactive tickets — monthly
Proactive: detected by platform before client · Reactive: reported by client (CMMS / phone)
Proactive
Reactive
Tickets by resolution — monthly
How tickets were closed during each month
Avoided truck roll
Dispatched
Consolidated
Discarded
Tickets by criticality — monthly