GroceriesSupermarketsTottus #001—Las Condes, Santiago
April 2026
Overview
HVAC
Refrigeration
Lighting
Energy
Tottus #001
Av. Apoquindo 4500
Las Condes, Santiago — Chile
5HVAC zones
8chambers
11cases
30lighting zones
6meters
Sales floor: 39,800 sq ft · ~3,700 m²
Hours: 08:00–22:00 · daily
Gateway GW-CL-001
Online
Last seen 3 min ago
Site at a glance
Site type
Supermarket
Peer cluster
Supermarket · 12 sites
Annual EUI estimate
720 kWh/m²/yr
Cluster percentile
38th · below median
Compliance & energy — selected period
Energy consumption — last 13 months
Site main meter monthly totals · does not respond to period selector
Trend · 13mo
kWh consumption
Peak demand (kW)
HVAC zones — current temperature
Pasillo 1
In band
71.2°F
target20–22°C
Pasillo 5
Drifting
75.4°F
target20–22°C
Pasillo 9
Drifting
72.0°F
target20–22°C
Pasillo 12
In band
70.8°F
target20–22°C
Pasillo 15
Drifting
74.6°F
target20–22°C
Top 5 non-compliant refrigeration items
Lowest compliance % in the selected period · chambers + display cases
Asset
Type
Current temp
Target range
Compliance
Status
Cámara Pescado
Chamber · Refrig
37.4°F
30–36°F
88.2%
Action needed
Mural Carne refrigerada 2
Case · Refrig
40.6°F
32–39°F
91.4%
Watch
Cámara Helados
Chamber · Frozen
2.1°F
-8 – 0°F
92.8%
Watch
Mural Bebidas No-Alcohólicas
Case · Refrig
46.3°F
37–45°F
93.6%
Watch
Cámara Lácteos
Chamber · Refrig
44.2°F
36–43°F
94.1%
Watch
Lighting at a glance
Zones on
26 / 30
Zones off
4 / 30
On schedule
98.4%
kWh in period
85,100
Energy meter mix
HVAC — sales floor temperature compliance
Operating hours:
Mon–Sat 08:30–21:30 · Sun 09:00–21:00 — compliance is computed only during these hours; off-hours are excluded. The compliance heatmap below is split into two grids (Mon–Sat and Sun) so each schedule is read against its own samples.
Filter zones
All zones
Pasillo 1
Pasillo 5
Pasillo 9
Pasillo 12
Pasillo 15
Per zone — sales floor temperature
Current reading + selected-period compliance · target band20–22°C · operating hours only
Zone
Current temp (live)
Avg temp (period)
Target range
Compliance (period)
Status
Pasillo 1
71.2°F
71.0°F
20–22°C
89.0%
In compliance
Pasillo 5
75.4°F
75.2°F
20–22°C
21.0%
Action needed
Pasillo 9
72.0°F
72.0°F
20–22°C
59.0%
Watch
Pasillo 12
70.8°F
70.8°F
20–22°C
93.0%
In compliance
Pasillo 15
74.6°F
74.5°F
20–22°C
31.0%
Action needed
Temperature evolution · selected period
One line per zone · each point summarizes the period in its natural unit (hour / day / week / month, depending on the selector) · operating-hours samples only · shaded band = target range
Pasillo 1
Pasillo 5
Pasillo 9
Pasillo 12
Pasillo 15
Operating hours · Mon–Sat 08:30–21:30 · Sun 09:00–21:00 — target band is only enforced during these windows.
Compliance heatmap — zone × hour
Split by schedule: Mon–Sat (08:30–21:30) on top, Sun (09:00–21:00) below · each cell shows compliance % for one zone in one hour-of-day · green = ≥95%, yellow = 90–95%, red = below 90% · gray = outside operating hours (N/A)
≥ 95%
90–95%
< 90%
N/A (closed)
Mon–Sat · 08:30–21:30
Compliance computed from Mon–Sat samples only
Sun · 09:00–21:00
Compliance computed from Sun samples only
Off-hours — overnight HVAC use (store closed)POC · to be confirmed
Proof of concept — to be confirmed. Metric definitions, thresholds and the outdoor model are illustrative and pending validation with real sub-15-min telemetry.During opening hours the concern is comfort; overnight it is energy — is the HVAC running while the store is closed? We infer it from the sales-floor temperature shape, in two tiers (without / with outdoor temperature).
Zone — overnight detail
Pasillo 1
Pasillo 5
Pasillo 9
Pasillo 12
Pasillo 15
Overnight temperature — closed window (21:30 → 08:30)
Indoor (10-min) · dashed grey = expected free-float toward outdoor · blue = outdoor · shaded = conditioning gap
Illustrative synthesized night. Cycling detection needs ≤5-min sampling. Cycling ≠ waste — a correct night setback also cycles. Refrigeration cases cycle in the same band: corroborate with BMS runtime / a submeter before assigning to HVAC. Outdoor from a weather API (Open-Meteo) by site coordinates.
Door activity — refrigerationPOC · to be confirmed
Proof of concept — door-open sensor metrics from a reed switch, correlated with unit temperature. Thresholds illustrative, pending validation. The sensor is binary (open/closed only); "closed" does not mean "not leaking".
Per asset — door metrics
Openings, open-time, door-ajar and door-attributed excursions · selected period
Door-open pattern — by hour
Openings per hour-of-day for the worst asset · expected restock peaks vs anomalous spikes
Caveats: binary sensor. "Closed" ≠ not leaking. DAE is an air proxy → manual product check, never auto-condemn. Freezer excursions are quality/frost. Open multideck cases have no door → excluded. % time open = load indicator, not metered energy.
Filter by category
All
Beef
White meats
Seafood
Dairy
Produce
Beverages
Frozen
Refrigeration assets — chambers + cases
One row per asset · chambers and cases mixed · category-filtered · period-driven compliance · click a row to drill into its telemetry
Asset
Type
Category
Current temp
Target range
Compliance
Status
Telemetry
One line for the selected asset · target band shaded · period-driven · click a row above to switch asset
Door-open events
Bar per hour-of-day · selected chamber only · cases hide this chart (no door)
Lighting — site KPIs
Power draw — 24h
From the Iluminación submeter · 15-min intervals · today
kWh trend — selected period
One bar per day (or hour for Day) · responds to period selector
Lighting zones — 30 zones
Per zone state + selected-period totals · schedule compliance computed against the zone's defined on/off schedule
Zone
Status
Hours used
Schedule compliance
Energy
Data source:
meter and bill data only. No weather normalization, no carbon estimates, no inferred domain disaggregation beyond the installed submeters.
Source:
Bill data is available only for Month / Quarter / YTD.Site type:Supermarket · Cluster:18 sites